Home › NZ Building Code › Energy & H1 › R-value Targets
NZ Building Code · Energy & H1R-value targets: the numbers your thermal envelope has to hit
The construction R-values each part of your build’s thermal envelope must reach under H1/AS1 — and why the framing behind the lining quietly drags them down.
R-value targets are the construction R-values each part of your thermal envelope must reach — the resistance of the whole built-up assembly once timber and gaps are accounted for, not just the insulation product on its own. Higher number = warmer, drier and cheaper to heat, so it pays to know what you’re actually building to before you order batts.
Targets by element
These are the H1/AS1 construction R-value targets by part of the envelope. Some are the same everywhere; others step up the further south (colder) you build. Zones run 1 (warm — upper North Island) to 6 (cold — Central Otago / inland South Island).
- Roof / ceiling: R6.6 — all zones.
- Wall: R2.0 — all zones.
- Slab on ground: R1.5 (zones 1–3) rising to R3.0 (zone 6) — and higher again if the slab is heated.
- Suspended floor: R1.5 (zones 1–3) rising to R2.5 (zones 4–6).
- Windows / glazing: R0.46 (zones 1–2) rising to R0.50 (zones 3–6).
Framing fraction — the catch on walls
Timber conducts heat around 3–4× faster than insulation, so the more framing in the wall, the lower the real R-value you end up with. H1/AS1 assumes a default framing fraction of roughly 38% for walls, but BRANZ has measured real walls anywhere from 24% to 57% — all the dwangs, trimmers and multi-stud corners push it up.
If your design is framing-heavy, use the actual fraction rather than the default. It’s more honest and it stops you signing off an overstated R-value that the wall never really achieves.
Hitting wall R2.0 in practice
Hitting the wall target on paper and hitting it in the real assembly aren’t the same thing. A bare 90×45 wall with R2.6 batts only reaches about R2.0 once thermal bridging is counted — and only if nothing’s compressed. Here’s the reliable build-up:
- 90×45 framing.
- An R2.2–2.6 batt between the studs.
- A 45 mm service cavity — battens running across the studs, insulated — so wiring and plumbing don’t crush the insulation, and the cavity adds resistance over the bridges.
Plain-English guide, not advice. This page helps you understand and navigate the rules — it is general information, not design, engineering or consent advice, and it does not reproduce the copyrighted tables of NZS 3604 or any Standard. Always check the current Standard or Acceptable Solution and your BCA, and use a suitably qualified LBP, engineer or QS where it matters.
Do it in Toolie
Put this into practice with the H1 R-value calculator · the insulation calculator · H1 6th edition. Try Toolie free — no signup — or open this topic in the Toolie app.
Common questions
What are the H1/AS1 R-value targets for roof and walls?
Roof or ceiling is R6.6 and walls are R2.0, both across all climate zones. These are construction R-values — the resistance of the whole built-up assembly once timber and gaps are counted, not just the insulation product.
Which R-value targets change with climate zone?
Slab on ground runs from R1.5 in zones 1–3 up to R3.0 in zone 6 (higher again if the slab is heated). Suspended floors go from R1.5 (zones 1–3) to R2.5 (zones 4–6), and glazing from R0.46 (zones 1–2) to R0.50 (zones 3–6). Zones run 1 (warm) to 6 (cold).
What is the framing fraction and why does it matter?
Timber conducts heat about 3–4× faster than insulation, so more framing means a lower real R-value. H1/AS1 assumes a default framing fraction of roughly 38% for walls, but BRANZ has measured real walls from 24% to 57%. If your design is framing-heavy, use the actual fraction so you don’t overstate the R-value.
How do you actually reach wall R2.0 on site?
A bare 90×45 wall with R2.6 batts only reaches about R2.0 once bridging is counted, and only if nothing’s compressed. A reliable build-up is 90×45 framing plus an R2.2–2.6 batt plus a 45 mm insulated service cavity, so wiring and plumbing don’t crush the insulation and the cavity adds resistance over the bridges.
More in Energy & H1
Quote it, comply, get paid — in one app
Toolie turns this knowledge into the job: NZS 3604 take-off, H1 & Healthy Homes, consents, retentions and invoicing — one flat NZD price.
Quote a job free →